FIRE HYDRANT FLOW TESTING

Fire Hydrant Testing (Pressure and Flow Simulation)

Fire safety is critical for all facilities and property owners and annual (or bi-annual) fire hydrant testing is used to determine the security of access to water for fire brigades in the event of a fire occurring.

BS9990: The fire hydrant testing procedure includes logging the pressure and establishing the maximum sustainable flow rate from each fire hydrant. The condition of the hydrant chamber and each fire hydrant is assessed and recorded in accordance with the BS:9990 criteria.

Fire Hydrant flow testing and condition assessment is essential to certify a fire hydrant’s optimum performance, and provides evidence of compliance with your fire certificate.

Typical large sites requiring Fire Hydrant Testing:

Hospital
Manufacturing/Pharmaceutical Plants
Business Parks
Factories
Universities
Residential Parks

Hydrant Testing and maintenance should be conducted for both insurance purposes and to ensure operability if a fire was to occur.

Lowflo provides a nationwide team of hydrant technicians who provide the following as part of your fire hydrant maintenance programme.

  • Uninhibited flow tests
  • Static pressure tests
  • Pit inspections
  • Frost valve checks

Dry Riser Testing

Lowflo provides two types of service in accordance with BS 9990:

  • Visual inspection
  • Annual pressure and flow test service
  • Test the riser with water and pressurise to 10 bar measured at the inlet for a period not less than 15 minutes
  • Whilst test is in progress check entire system for any obvious leakage
  • No appreciable loss in pressure (0.5 bar)
  • Drain dry riser completely on completion

Where faults are located Lowflo can also conduct the repairs live or by shutting down the fire system – CLICK HERE to read more on our Repair Teams.

HELPFUL LINKS

How do we find leaks? – CLICK HERE

Domestic Services – CLICK HERE

Our Customers – CLICK HERE

For proactive water management for your facility please contact us about the Lowflo – AQUAPACK

FREEPHONE 1800 220 220
We Guarantee you will speak with one of our Engineers within 5 minutes.
Fire Hydrant Testing on pumped system using dry barrel hydrants

FREEPHONE
1800 220 220

We Guarantee you will speak with one
of our Engineers within 5 minutes.

Download the 
Lowflo Brochure 2017

ENQUIRY FORM